Size the battery to inverter cable

Checks whether the voltage at the inverter input stays above the cut-off under surge load. This is the number one failure in self-built systems: the inverter trips on undervoltage when the compressor starts, while the battery is still half full. Calculated from the minimum battery voltage, not the nominal one.

Input

Input

Largest inrush event plus base load — from the load profile.

Cutoff voltage — the worst and governing case.

Undervoltage shutdown threshold from the inverter datasheet.

Unchecked, the page proposes the required cross-section; checked, it tests your cable against both criteria.

Result · Live

Recommended cross-section
25mm²sized for the peak current at an empty battery
Peak current
294Aat cutoff voltage — where it is highest
Voltage at the inverter
11.37Vunder peak load, after the cable drop
Headroom to cutoff
0.87Vif it goes negative, the inverter disconnects at compressor start
  • Only 0.87 V remain to the 10.5 V cut-off. A colder cable, a few centimetres more run, or a slightly lower state of charge can tip this over.CUTOFF_MARGIN_THIN
  • Length is the one-way run. The factor of 2 for the return conductor is already in the formula.LENGTH_INTERPRETATION
  • This size satisfies voltage drop. Ampacity must be checked separately — 92.59 A is required.AMPACITY_SEPARATE_CHECK
Peak-load profile with 25 mm²
shutdown threshold 10.5 V battery 12 V inverter 11.37 V −0.63 V cable drop at peak

At peak load and empty battery, 0.87 V of headroom remain to the shutdown threshold — the cable carries the worst case.

Calculation steps
  • Continuous current: P_cont / (U_bat,min * eta) = 92.593 A
  • Peak current: P_peak / (U_bat,min * eta_peak) = 294.12 A
  • Voltage at the inverter under surge: U_bat,min - 2 * rho * L * I_peak / A = 11.368 V

The formulas behind the calculator

Every number above can be recomputed: the full calculation path, all assumptions and the data source with retrieval date — plus cross-validation against independent references. Disclosed, not claimed.

Safety-relevant calculation. This is an estimate based on the stated assumptions. The final design must be checked by a qualified electrician against the rules that apply where you are.

Data as of: 2026-07-15 · The technical review of this safety-relevant calculator is still outstanding.

Every intermediate value with its formula, number and provenance
StepFormulaValueProvenance
Continuous currentP_cont / (U_bat,min * eta)92.593 Aexact
Peak currentP_peak / (U_bat,min * eta_peak)294.12 Aexact
Voltage at the inverter under surgeU_bat,min - 2 * rho * L * I_peak / A11.368 Vexact
Formula
U_inv = U_bat,min − 2 · ρ(T) · L · I_peak / A
Valid for
Currents from the MINIMUM battery voltage (3,000 W / 12.0 V → 294 A peak; nominal would give only 267 A); two criteria per size: continuous-load drop against the manufacturer limit (typically 2 %) and voltage at the inverter cutoff plus margin at peak current. Sizing and check modes (existing cable) selectable. Reference: sizing → 25 mm²; 16 mm² fails both criteria, 35 mm² passes. Ampacity is the separate second check (calculator 18).
Not covered
Contact resistances at terminals and fuse holders (they consume the margin — noted in the FAQ), ampacity with installation method (calculator 18), fusing (calculator 16), mechanical routing and chafe protection, paralleling several banks (calculator 22).
Data sources
  • Official publications of the standards bodies and state authorities (NFPA, IEC, DKE/VDE, CEN) · retrieved 2026-07-15

Frequently asked questions

What cable size do I need between the battery and the inverter?

The calculator picks the smallest cross-section that satisfies two conditions at once: the continuous voltage-drop limit (typically 2 % per manufacturer guidance) and the cut-off check under surge load. On a short 1.5 m run the percentage limit is easily met while the cut-off threshold is still violated — which is why a plain percentage calculator is not enough here.

Why does my inverter trip on undervoltage even though the battery is half full?

This is the number one failure in self-built systems: during a compressor start the surge current flows, and the drop in the battery cable pushes the voltage at the inverter input below its cut-off — the battery is not the problem. The calculator checks V_at_inverter = V_batt,min − 2 · ρ(T) · L · I_surge / A against the cut-off plus a safety margin. It uses the minimum battery voltage, because surge loads occur precisely at low state of charge.

Does the calculator account for the battery's internal resistance?

No — the battery's internal resistance and the additional sag it causes are not modelled, nor are contact resistances at terminals and isolators or the dynamic behaviour in the first milliseconds. The cable's ampacity is a separate check, which the result explicitly flags.

Why is the battery cable sized for the empty battery?

Because current is highest there: the same 3,000 W peak load draws half again as much current at 10.0 V cutoff as at 14.4 V charge end. And exactly at an empty battery comes the worst moment — at night, the fridge compressor starts, the voltage sags. Calculating with nominal voltage sizes the cable for the fair-weather case.

My inverter shuts down at compressor start although the battery is half full — why?

The classic symptom of a too-thin battery cable: at inrush, so much voltage drops across the cable that the inverter momentarily sees less than its shutdown threshold — it disconnects although the battery has plenty of energy. The voltage profile in the chart shows exactly this path; the headroom tile says how much air remains. Remedy: next cross-section or shorter runs, not more battery.

Do joints and fuses in the battery circuit count?

Yes — every terminal, shunt and fuse adds milliohms that cost volts at peak current. The calculator models the cable drop; for the joints the busbar rule applies: assemble cleanly, torque to spec, retorque after the first month. With tight headroom the joints are often the difference between “runs” and “disconnects”.

Can I have an existing cable checked?

Yes — since 5 August 2026 via the “check an existing cable” switch. The page then tests your cross-section against both criteria: the permissible continuous-load voltage drop and the cutoff-threshold margin at peak current. In the reference case 16 mm² fails (drop above limit, thin margin to the cutoff), 35 mm² passes cleanly. Unchecked, the page proposes the required size as before — 25 mm².

Why does my inverter cut out although the battery is half full?

Almost always because of the battery cable, not the battery: on compressor start the inverter draws 294 A in the reference case — with too thin a cable the voltage at the inverter input sags below the cutoff threshold although the battery terminals still hold enough. Exactly this check is the page's core: voltage at the threshold plus required margin, computed at peak current.

Why compute with the minimum battery voltage?

Because peak load strikes exactly when the battery is weak — and current is highest at low voltage: 3,000 W at a 12.0 V minimum is 294 A; computed at nominal voltage it would be only 267 A. Sizing at nominal buys the cable one size too small, discovered on the first winter evening.

Is the voltage-drop check sufficient for the battery cable?

No — ampacity is the second, independent check, and at 92.6 A continuous it is often the stricter one. The page says so explicitly as its own note; the ampacity proof with installation method and correction factors lives in the ampacity calculator. Both must pass, plus fusing (DC calculator) and a short, protected run.

What does the cutoff margin mean concretely?

The distance between the voltage at the inverter at peak current and its undervoltage cutoff. The 0.5 V default is deliberately tight — contact resistances at terminals and fuse holders add in practice and are not included here. Crimped ring lugs and clean junctions preserve the margin; corroded clamps eat it.